This battery is typically used as a replacement battery in UPS systems, security alarm systems or security lighting applications.
Application

Specifications
| Physical Characteristics |
| Type |
UPS Replacement |
| Absorbed Glass Mat (AGM) |
Yes |
| Voltage |
6V |
| Amps |
5A |
| Terminal Type |
F1 |
| Tab Size |
0.1875 inch |
| Container Material |
ABS(UL-94HB) |
| Length |
1.85 inches [47mm] |
| Width |
2.8 inches [70mm] |
| Height |
4 inches [102mm] |
| Operating Temperature |
25±3℃ (77±5℉ ) |
| Performance |
| Internal Resistance |
Approx.15mmΩ
|
| Max. Discharge Current |
105A(5S) |
| Rated Capacity |
5.00AH (20hr, 1.75V/cell,25℃/77℉) 4.72AH (10hr, 1.75V/cell,25℃/77℉) 4.23AH (5hr, 1.75V/cell,25℃/77℉) 3.85AH (3hr, 1.75V/cell,25℃/77℉) 2.89AH (1hr, 1.75V/cell,25℃/77℉) |
| Cycle Use |
Charge Current Less Than 0.25CA 7.05V~7.35V@25℃(77℉)Temp. Coefficient -30mV/℃ |
| Floating Use |
No limit on Initial Charging Current Voltage 6.75V~6.9V@25℃(77℉)Temp. Coefficient -20mV/℃ |
Capacity affected by Temperature |
40℃ 103% 25℃ 100% 0℃ 86% -15℃ 65% |
| Self-discharge |
3 month Remaining capacity: 91% 6 month Remaining capacity:82% 12 month Remaining capacity:65% |
| Packaging Information |
| Product Weight |
1.9lbs [0.9kg] |
| Warranty Information |
| Warranty |
6 Months |